SPS logo

Manufacturer Representatives of Quality Engineered Control Panel Products in Motor Control, Power Reliability, Explosion-Proof Control Systems, and Fully-Integrated Low and Medium Voltage Solutions

IEC Utilization Categories

AC CategoryTypical ApplicationSwitchgear Standard
AC 1Non Inductive or Slightly inductive loads, with Power Factor greater than 0.95, eg: Resistive load, heating. Switchgear: Electromechanical contactors. Operation: Switching.IEC 60947-4-1
AC 2Slip-ring motor.Switchgear: Electromechanical contactors. Operation: Switching off.IEC 60947-4-1
AC 3Squirrel cage motors. Switchgear: Electromechanical contactors. Operation : Starting, Switching off during running.IEC 60947-4-1
AC 4Squirrel cage motor. Switchgear: Electromechanical contactors. Operation: Starting, Plugging, Inching.IEC 60947-4-1
AC 5aDischarge lamps. Switchgear: Electromechanical contactors. Operation: Switching.IEC 60947-4-1
AC5bIncandescent lamps. Switchgear: Electromechanical contactors. Operation: Switching.IEC 60947-4-1
AC 6aTransformers. Switchgear: Electromechanical contactors. Operation: Switching.IEC 60947-4-1
AC 6bCapacitor banks. Switchgear: Electromechanical contactors. Operation: Switching.IEC 60947-4-1
AC 7aSlightly Inductive Household load, eg. Mixer. Switchgear: Electromechanical contactors for household purpose, eg. Miniature Contactor. Operation: Switching.IEC 61095
AC 7bHousehold motor loads, eg; Fan, Vaccume pump motor. Switchgear: Electromechanical contactors for household purpose, eg. Miniature Contactor. Operation: Switching, occasional inching, pluggingIEC 61095
AC 7cCompensated electric discharge lamp control. Switchgear: Electromechanical contactors for household purpose, eg. Miniature Contactor. Operation: Switching.IEC 61095
AC 8aHermetic refrigerant compressor motor. Switchgear: Electromechanical contactors. Operation: Manual resetting overload control.IEC 60947-4-1
AC 8bHermetic refrigerant compressor motor. Switchgear: Electromechanical contactors. Operation: Automatic resetting overload control.IEC 60947-4-1
AC 12Resistive and solid state load with Opto-coupler Isolation. Switchgear: Electromechanical control circuit devices, eg. Aux Contacts. Operation: Switching, Control.IEC 60947-5-1
AC 13Solid state load with transformer Isolation. Switchgear: Electromechanical control circuit devices, eg. Aux Contacts. Operation: Switching, Control.IEC 60947-5-1
AC 14Small Electromagnetic loads. Switchgear: Electromechanical control circuit devices, eg. Aux Contacts. Operation: Switching, Control.IEC 60947-5-1
AC 15AC Electromagnetic loads. Switchgear: Electromechanical control circuit devices, eg. Aux Contacts. Operation: Switching, Control.IEC 60947-5-1
AC 20AAll. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching under no load condition. Frequent operation.IEC 60947-3
AC 20BAll. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Infrequent operation.IEC 60947-3
AC 21AResistive load with moderate overload. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Frequent operation.IEC 60947-3
AC 21BResistive load with moderate overload. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Infrequent operation.IEC 60947-3
AC 22AMix Resistive and Inductive loads with moderate overload. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Frequent operation.IEC 60947-3
AC 22BMix Resistive and Inductive loads with moderate overload. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Infrequent operation.IEC 60947-3
AC 23AHighly Inductive load, eg: Motor. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Frequent operation.IEC 60947-3
AC 23BHighly Inductive load, eg: Motor. Switchgear: Switches, disconnectors, switch-disconnectors. Operation: Switching. Infrequent operation.IEC 60947-3
AC 31ANon Inductive, slightly inductive. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With no rated short time withstand capacity.IEC 60947-6-1
AC 31BNon Inductive, slightly inductive. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With rated short time withstand capacity.IEC 60947-6-1
AC 32AMixed resistive and slightly inductive load with moderate overload. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With no rated short time withstand capacity.IEC 60947-6-1
AC 32BMixed resistive and slightly inductive load with moderate overload. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With rated short time withstand capacity.IEC 60947-6-1
AC 33AHighly Inductive load, eg: Motor. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With no rated short time withstand capacity.IEC 60947-6-1
AC 33BHighly Inductive load, eg: Motor. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching. With rated short time withstand capacity.IEC 60947-6-1
AC 35Electric discharge lamp. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS Operation: Switching.IEC 60947-6-1
AC 36Incandescent lamp. Switchgear: Multiple function equipment – Transfer switching equipment, eg: ATS. Operation: Switching.IEC 60947-6-1
AC 40Mix Resistive and Inductive loads. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Control & Switching.IEC 60947-6-2
AC 41Non Inductive, slightly inductive. eg: resistance furnace. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Control & Switching.IEC 60947-6-2
AC 42Slip-ring motor. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Control & Switching.IEC 60947-6-2
AC 43Squirrel cage motors. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Starting, Switching off during running.IEC 60947-6-2
AC 44Squirrel cage motors. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Starting, Plugging, Inching.IEC 60947-6-2
AC 45AElectric discharge lamp. Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Control & Switching.IEC 60947-6-2
AC 45BIncandescent Switchgear: CPS-Control and protective switching devices, eg. Integral Contactor breaker. Operation: Control & Switching.IEC 60947-6-2
AC 51ANon Inductive or Slightly inductive loads. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Switching.IEC 60947-4-2
AC 51BNon Inductive or Slightly inductive loads. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Switching.IEC 60947-4-2
AC 52ASlip ring motor. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Control of slip ring motor stators for 8 hour duty with on load current for start, acceleration & run.IEC 60947-4-2
AC 52BSlip ring motor. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Bypassed during motor running.IEC 60947-4-2
AC 53AControl of squirrel cage Induction motor on 8 hour duty with on load currentfor start, acceleration and run. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter.IEC 60947-4-2
AC 53BControl of squirrel cage induction motors on intermittent duty. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter.Operation: Soft-Starter Control. These Soft starters are bypassed during motor running.IEC 60947-4-2
AC 55AElectric Discharge lamp. Switchgear: AC semiconductor controllers and contactors for non-motor loads, eg. IGBT. Operation: Switching.IEC 60947-4-3
AC 55BIncandescent Switchgear: AC semiconductor controllers and contactors for non-motor loads, eg. IGBT. Operation: Switching.IEC 60947-4-3
AC 56ATransformer. Switchgear: AC semiconductor controllers and contactors for non-motor loads, eg. IGBT. Operation: Switching.IEC 60947-4-3
AC 56BCapacitor bank. Switchgear: AC semiconductor controllers and contactors for non-motor loads, eg. IGBT. Operation: Switching.IEC 60947-4-3
AC 58AHermetic refrigerant compressor motor with automatic resetting of overload releases. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Control for 8 hour duty with on load current for start, acceleration & run.IEC 60947-4-2
AC 58BHermetic refrigerant compressor motor with automatic resetting of overload releases. Switchgear: AC semiconductor motor controllers and starters, eg. Soft Starter. Operation: Start of Motor, then bypassed during motor running.IEC 60947-4-2
AC 140Small electromagnetic loads with holding (closed) current 0.2A or less. Switchgear: Control circuitdevices and switching elements – Proximity switches, eg. contactor relays Operation: Switching.IEC 60947-5-2

Referenced Standards